21242.99 18735.41 16168.15 13482.56 10672.55 7803.101 5515.961 2583.4 916.595 21545.32 18991.95 16368.81 13677.72 10836.56 7906.703 5586.949 2605.324 901.208 21253.84 18731.06 16160.03 13479.01 10694.58 7809.706 5518.311 2575.801 931.766 97.012 84.862 73.101 58.618 46.685 33.459 25.324 13.354 3.581 1279.071 1105.131 942.432 771.962 605.392 430.297 300.774 129.494 24.246 结论:与出厂试验值相符。 发电机空载特性曲线见下图:
惠来#3机空载特性曲线30000发电机机端电压(V)2500020000150001000050000050010001500励磁电流(A)20002500
上升曲线下降曲线f、#4发电机空载试验结果
发电机空载试验曲线: UAB(V) 2840.108 4994.972 7173.897 9392.866 11583.150 13766.970 15960.150 18062.670 19144.200 20213.250 21221.420 22221.710 23225.750 UBC(V) 2861.637 5029.209 7221.220 9451.356 11654.110 13866.750 16074.220 18193.180 19273.170 20355.580 21373.810 22382.700 23396.680 UCA(V) 2839.893 4999.425 7169.839 9390.446 11580.900 13769.000 15968.530 18066.760 19137.910 20217.060 21221.140 22229.760 23226.560 UFD(V) 16.987 26.299 36.491 45.921 55.752 65.491 74.890 85.140 90.508 95.448 101.578 108.074 114.021 ILD(A) 159.011 290.134 418.760 549.728 679.127 809.760 942.274 1075.173 1146.168 1217.319 1290.194 1366.158 1445.754 表中:UAB、UBC、UCA分别为发电机定子电压,IL、UL分别为发电机转子电流、电压。
结论:与出厂试验值相符。 发电机空载特性曲线见下图:
惠来#4号机发电机空载试验特性图25000发电机机端电压(V)2000015000上升曲线1000050000050010001500发电机励磁电流(A)2000
二、励磁装置检查
DCS画面上的励磁电流是经过9000A/100mV的分流器、0~100mV/4~20mA变送器送出的,检查#3、4发电机励磁电流,DCS画面上的励磁电流值与励磁调节器液晶屏显示值一致。 三、初步分析
自2013年1月启机以来,#3、4机组振动正常,经过上述试验结果比对及检查,未发现明显异常点,但由于机组运行,无法进行其他检查工作。 四、后续工作计划
1、就#3、4发电机励磁电流偏大情况,联系东电厂,协助分析(传真已发出,但还未回复)。 2、采购励磁电流变送器备品。
3、在3C、4C期间,进行励磁系统小电流试验,进行励磁电流比对。 4、启机过程中,进行发电机空载试验,进一步进行励磁电流比对。